Part numbers
##TABREF##
Specifications
|
| General environment characteristics for CB, CD, XD, XB, XR and XE product types | |
Certifications |
CE, UL, CSA
| |
Conformity to standards (with the low voltage directive and EMC directive) |
IEC/EN 61131-2 (Open equipment) IEC/EN 61131-2 (Zone B) IEC/EN 61000-6-2, IEC/EN 61000-6-3 (*) IEC/EN 61000-6-4 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure)
| |
Earthing |
None
| |
Protection rating |
In accordance with IEC/EN 60529 : IP40 on front panel IP20 on terminal block
| |
Overvoltage category |
3 in accordance with IEC/EN 60664-1
| |
Pollution |
Degree : 2 in accordance with IEC/EN 61131-2
| |
Max operating Altitude |
Operation : 2000 m Transport : 3,048 m
| |
Mechanical resistance |
Immunity to vibrations IEC/EN 60068-2-6, Fc test Immunity to shock IEC/EN 60068-2-27, Fa test
| |
Resistance to electrostatic discharge |
Immunity to ESD IEC/EN 61000-4-2, level 3
| |
Resistance to HF interference |
Immunity to radiated electrostatic fields IEC/EN 61000-4-3, Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12
| |
Conducted and radiated emissions |
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in metallic cabinet)
| |
Operating temperature |
-20 →+55 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-2-2
| |
Storage temperature |
-40 →+70 °C in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-2-2
| |
Relative humidity |
95 % max. (no condensation or dripping water) in accordance with IEC/EN 60068-2-30
| |
Mounting |
On symmetrical DIN profile, 35 x 7.5 mm and 35 mm x 15 or panel (2 x 4 mm Ø)
| |
Screw terminals connection capacity |
Flexible wire with ferrule = 1 conductor : 0.25 to 2.5 mm 2 (AWG 24...AWG 14) 2 conductors 0.25 to 0.75 mm 2 (AWG 24...AWG 18) Semi-rigid wire = 1 conductor : 0.2 to 2.5 mm 2 (AWG 25...AWG 14) Rigid wire = 1 conductor : 0.2 to 2.5 mm 2 (AWG 25...AWG 14) 2 conductors 0.2 to 1.5 mm 2 (AWG 25...AWG 16) Tightening torque = 0.5 N.m (4.5 lb-in) (tighten using screwdriver diam. 3.5 mm)
|
|
Processing characteristics of CB, CD, XD & XB product types | | |
LCD display |
CD, XD : Display with 4 lines of 18 characters
| |
Programming method |
Function blocks / SCF (Grafcet) or Ladder
| |
Program size |
128 macros maximum 256 blocks maximum per macro 64 typical blocks for CB, CD
| |
Program memory |
Flash EEPROM
| |
Removable memory |
EEPROM
| |
Data memory |
368 bit/200 words
| |
Back-up time in the event of power failure |
Program and settings in the controller : 10 years Program and settings in the plug-in memory : 10 years Data memory : 10 years
| |
Cycle time |
Function blocks : 6 →90 ms Ladder : typically 20 ms
| |
Response time |
Input acquisition time + 1 to 2 cycle times
| |
Clock data retention |
10 years (lithium battery) at 25 °C
| |
Clock drift |
Drift < 12 min/year (at 25 °C) 6 s/month (at 25 °C with user-definable correction of drift)
| |
Timer block accuracy |
1 % ± 2 cycle times
| |
Start up time on power up |
< 1,2 s
|
|
| Characteristics of products with AC power supplied |
|
Supply |
24 V AC (88970..4)
|
100 →240 V AC (88970..3)
| |
Nominal voltage |
24 V AC |
100 →240 V AC | |
Operating limits |
-15 % / +20 % or 20.4 VAC→28.8 VAC |
-15 % / +10 % or 85 VAC→264 VAC | |
Supply frequency range |
50/60 Hz (+4 % / -6 %) or 47→53 Hz/57 < 63 Hz
|
50/60 Hz (+4 % / -6 %) or 47 →53 Hz/57 < 63 Hz
| |
Immunity from micro power cuts |
10 ms (repetition 20 times)
|
10 ms (repetition 20 times)
| |
Max. absorbed power |
CB12-CD12-XD10-XB10 : 4 VA CB20-CD20 : 6 VA XD10 with extension - XD26-XB26 : 7.5 VA XD26-XB26 with extension : 10 VA
|
CB12-CD12-XD10-XB10 : 7 VA CB20-CD20 : 11 VA XD10-XB10 with extension-XD26-XB26 : 12 VA XD26-XB26 with extension : 17 VA
| |
Isolation voltage |
1780 V AC |
1780 V AC |
|
Inputs |
24 V AC (88970..4)
|
100 →240 V AC (88970..3)
| |
Input voltage |
24 V AC (-15 % / +20 %)
|
100 →240 V AC (-15 % / +10 %)
| |
Input current |
4,4 mA @ 20,4 V AC 5,2 mA @ 24,0 V AC 6,3 mA @ 28,8 V AC |
0,24 mA @ 85 V AC 0,75 mA @ 264 V AC | |
Input impedance |
4.6 kΩ |
350 kΩ | |
Logic 1 voltage threshold | ≥ 14 V AC | ≥ 79 V AC | |
Making current at logic state 1 |
>2 mA
|
>0.17 mA
| |
Logic 0 voltage threshold | ≤ 5 V AC | ≤ 20 V AC (≤ 28 V AC : XE10, XR06, XR10, XR14)
| |
Release current at logic state 0 |
<0.5 mA
|
<0.5 mA
| |
Response time with LADDER programming |
50 ms State 0 →1 (50/60 Hz)
|
50 ms State 0 < 1 (50/60 Hz)
| |
Response time with function blocks programming |
Configurable in increments of 10 ms 50 ms min. up to 255 ms State 0 →1 (50/60 Hz)
|
Configurable in increments of 10 ms 50 ms min. up to 255 ms State 0 →1 (50/60 Hz)
| |
Maximum counting frequency |
In accordance with cycle time (Tc) and input response time (Tr) : 1/ ( (2 x Tc) + Tr)
|
In accordance with cycle time (Tc) and input response time (Tr) : 1/ ( (2 x Tc) + Tr)
| |
Sensor type |
Contact or 3-wire PNP
|
Contact or 3-wire PNP
| |
Input type |
Resistive
|
Resistive
| |
Isolation between power supply and inputs |
None
|
None
| |
Isolation between inputs |
None
|
None
| |
Protection against polarity inversions |
Yes
|
Yes
| |
Status indicator |
On LCD screen for CD and XD
|
On LCD screen for CD and XD
|
|
| Characteristics of relay outputs common to the entire range | |
Max. breaking voltage |
5 →30 V DC 24 →250 V AC | |
Breaking current |
CB-CD-XB10-XD10-XR06-XR10 : 8 A XD26-XB26 : 8 x 8 A relays, 2 x 5 A relays XE10 : 4 x 5 A relays XR14 : 4 x 8 A relays, 2 x 5 A relays
| |
Electrical durability for 500 000 operating cycles |
Usage category DC-12 : 24 V, 1.5 A Usage category DC-13 : 24 V (L/R = 10 ms), 0.6 A Usage category AC-12 : 230 V, 1.5 A Usage category AC-15 : 230 V, 0.9 A
| |
Max. Output Common Current |
12A for O8,O9,OA
| |
Minimum switching capacity |
10 mA (at minimum voltage of 12 V)
| |
Minimum load |
12 V, 10 mA
| |
Maximum rate |
Off load : 10 Hz At operating current : 0.1 Hz
| |
Mechanical life |
10,000,000 operations (cycles)
| |
Voltage for withstanding shocks |
In accordance with IEC/EN 60947-1 and IEC/EN 60664-1 : 4 kV
| |
Response time |
Make 10 ms Release 5 ms
| |
Built-in protections |
Against short-circuits : None Against overvoltages and overloads : None
| |
Status indicator |
On LCD screen for CD and XD
|
|
| Characteristics of product with DC power supplied |
|
Supply |
12 V DC (88970..5 & 8970814 & 88970840)
|
24 V DC (88970..1 et 88970..2)
| |
Nominal voltage |
12 V DC |
24 V DC | |
Operating limits |
-13 % / +20 % or 10.4 V DC < 14.4 V DC (including ripple)
|
-20 % / +25 % or 19.2 V DC < 30 V DC (including ripple)
| |
Immunity from micro power cuts | ≤ 1 ms (repetition 20 times)
| ≤ 1 ms (repetition 20 times)
| |
Max. absorbed power |
CB12 with solid state outputs : 1.5 W CD12 : 1.5 W CD20 : 2.5 W XD26-XB26 : 3 W XD26-XB26 with extension : 5 W XD26 with solid state outputs : 2.5 W
|
CB12-CD12-CD20 with solid state outputs - XD10-XB10 with solid state outputs : 3 W XD10-XB10 with relay outputs : 4 W XD26-XB26 with solid state outputs : 5 W CB20-CD20 with relay outputs-XD26 with relay outputs : 6 W XD10-XB10 with extension : 8 W XD26-XB26 with extension : 10 W
| |
Protection against polarity inversions |
Yes
|
Yes
|
|
Digital inputs (I1 to IA and IH to IY) |
12 V DC (88970..5 & 88970814 & 88970840)
|
24 V DC (88970..1 and 88970..2)
| |
Input voltage |
12 V DC (-13 % / +20 %)
|
24 V DC (-20 % / +25 %)
| |
Input current |
3,9 mA @ 10,44 V DC 4,4 mA @ 12,0 V DC 5,3 mA @ 14,4 VDC |
2,6 mA @ 19,2 V DC 3,2 mA @ 24 V DC 4,0 mA @ 30,0 VDC | |
Input impedance |
2.7 kΩ |
7.4 kΩ | |
Logic 1 voltage threshold | ≥ 7 V DC | ≥ 15 V DC | |
Making current at logic state 1 | ≥2 mA
| ≥2.2 mA
| |
Logic 0 voltage threshold | ≤ 3 V DC | ≤ 5 V DC | |
Release current at logic state 0 |
<0.9 mA
|
<0.75 mA
| |
Response time |
1 →2 cycle times + 6 ms
|
1 →2 cycle times + 6 ms
| |
Maximum counting frequency |
I1 & I2 : FBD (Up to 6 k Hz) & Ladder (1 k Hz) I3 to IA & IH to IY : in accordance with cycle time (Tc) and input response time (Tr) : 1/ ( (2 x Tc) + Tr)
|
I1 & I2 : FBD (Up to 6 k Hz) & Ladder (1 k Hz) I3 to IA & IH to IY : in accordance with cycle time (Tc) and input response time (Tr) : 1/ ( (2 x Tc) + Tr)
| |
Sensor type |
Contact or 3-wire PNP
|
Contact or 3-wire PNP
| |
Conforming to IEC/EN 61131-2 |
Type 1
|
Type 1
| |
Input type |
Resistive
|
Resistive
| |
Isolation between power supply and inputs |
None
|
None
| |
Isolation between inputs |
None
|
None
| |
Protection against polarity inversions |
Yes
|
Yes
| |
Status indicator |
On LCD screen for CD and XD
|
On LCD screen for CD and XD
|
|
Analogue or digital inputs (IB to IG) |
12 V DC (88970..5 & 88970814 & 88970840)
|
24 V DC (88970..1 and 88970..2)
| |
CB12-CD12-XD10-XB10 |
4 inputs IB →IE
|
4 inputs IB →IE
| |
CB20-CD20-XB26-XD26 |
6 inputs IB →IG
|
6 inputs IB →IG
|
|
Inputs used as analogue inputsonly in FBD | | | |
Measurement range |
(0 →10 V) or (0 →V power supply)
|
(0 →10 V) or (0 →V power supply)
| |
Input impedance |
14 kΩ |
12 kΩ | |
Input voltage |
14.4 V DC max
|
30 V DC max
| |
Value of LSB |
14 mV
|
29 mV
| |
Input type |
Common mode
|
Common mode
| |
Resolution |
10 bit at maximum input voltage
|
10 bit at maximum input voltage
| |
Conversion time |
Controller cycle time
|
Controller cycle time
| |
Accuracy at 25 °C | ± 5 %
| ± 5 %
| |
Accuracy at 55 °C | ± 6.2 %
| ± 6.2 %
| |
Repeat accuracy at 55 °C | ± 2 %
| ± 2 %
| |
Isolation between analogue channel and power supply |
None
|
None
| |
Cable length |
10 m maximum, with shielded cable (sensor not isolated)
|
10 m maximum, with shielded cable (sensor not isolated)
| |
Protection against polarity inversions |
Yes
|
Yes
| |
Potentiometer control |
2.2 kΩ/0.5 W (recommended) 10 kΩ max.
|
2.2 kΩ/0.5 W (recommended) 10 kΩ max.
|
|
Inputs used as digital inputs | | | |
Input voltage |
12 V DC (-13 % / +20 %)
|
24 V DC (-20 % / +25 %)
| |
Input current |
0,7 mA @ 10,44 VDC 0,9 mA @ 12,0 VDC 1,0 mA @ 14,4VDC |
1,6 mA @ 19,2 VDC 2,0 mA @ 24,0 V DC 2,5 mA @ 30,0 VDC | |
Input impedance |
14 kΩ |
12 kΩ | |
Logic 1 voltage threshold | ≥ 7 V DC | ≥ 15 VDC | |
Making current at logic state 1 | ≥0.5 mA
| ≥1.2 mA
| |
Logic 0 voltage threshold | ≤ 3 V DC | ≤ 5 V DC | |
Release current at logic state 0 | ≤0.2 mA
| ≤0.5 mA
| |
Response time |
1 →2 cycle times
|
1 →2 cycle times
| |
Maximum counting frequency in FBD |
In accordance with cycle time (Tc) and input response time (Tr) : 1/ ( (2 x Tc) + Tr)
|
In accordance with cycle time (Tc) and input response time (Tr) : 1/ ( (2 x Tc) + Tr)
| |
Sensor type |
Contact or 3-wire PNP
|
Contact or 3-wire PNP
| |
Conforming to IEC/EN 61131-2 |
Type 1
|
Type 1
| |
Input type |
Resistive
|
Resistive
| |
Isolation between power supply and inputs |
None
|
None
| |
Isolation between inputs |
None
|
None
| |
Protection against polarity inversions |
Yes
|
Yes
| |
Status indicator |
On LCD screen for CD and XD
|
On LCD screen for CD and XD
|
|
Characteristics of relay outputs common to the entire range | | |
Max. breaking voltage |
5 →30 V DC 24 →250 V AC | |
Max. Output Common Current |
12A (10A UL) for O8,O9,OA
| |
Breaking current |
CB-CD-XD10-XB10-XR06-XR10 : 8 A XD26-XB26 : 8 x 8 A relays, 2 x 5 A relays XE10 : 4 x 5 A relays XR14 : 4 x 8 A relays, 2 x 5 A relays
| |
Electrical durability for 500 000 operating cycles |
Usage category DC-12 : 24 V, 1.5 A Usage category DC-13 : 24 V (L/R = 10 ms), 0.6 A Usage category AC-12 : 230 V, 1.5 A Usage category AC-15 : 230 V, 0.9 A
| |
Minimum switching capacity |
10 mA (at minimum voltage of 12 V)
| |
Minimum load |
12 V, 10 mA
| |
Maximum rate |
Off load : 10 Hz At operating current : 0.1 Hz
| |
Mechanical life |
10,000,000 operations (cycles)
| |
Voltage for withstanding shocks |
In accordance with IEC/EN 60947-1 and IEC/EN 60664-1 : 4 kV
| |
Response time |
Make 10 ms Release 5 ms
| |
Built-in protections |
Against short-circuits : None Against overvoltages and overloads : None
| |
Status indicator |
On LCD screen for CD and XD
|
|
Digital / PWM solid state output |
12 V DC (88970814 & 88970840)
|
24 V DC (88970..2)
| |
PWM solid state output* |
CB12 : O4 XD26 : O4 →O7
|
CD12-XD10-XB10 : O4 CD20-XD26-XB26 : O4 →O7
| |
* Only available with "FBD" programming language
|
* Only available with "FBD" programming language
| |
Breaking voltage |
10.4 →30 VDC |
19.2 →30 VDC | |
Nominal voltage |
12-24 V DC |
24 V DC | |
Nominal current |
0.5 A
|
0.5 A
| |
Max. breaking current |
0,625 A
|
0,625 A
| |
Voltage drop | ≤ 2 V for I = 0.5 A (at state 1)
| ≤ 2 V for I = 0.5 A (at state 1)
| |
Response time |
Make ≤ 1 ms Release ≤ 1 ms
|
Make ≤ 1 ms Release ≤ 1 ms
| |
Frequency (Hz) |
1 Maximum on inductive load
|
1 Maximum on inductive load
| |
Built-in protections |
Against overloads and short-circuits : Yes Against overvoltages (*) : Yes Against inversions of power supply : Yes (*) In the absence of a volt-free contact between the output of the logic controller and the load
|
Against overloads and short-circuits : Yes Against overvoltages (*) : Yes Against inversions of power supply : Yes (*) In the absence of a volt-free contact between the output of the logic controller and the load
| |
Min. load |
1 mA
|
1 mA
| |
Maximum incandescent load |
0,2 A / 12 V DC 0,1 A / 24 V DC |
0,1 A / 24 V DC | |
Galvanic isolation |
No
|
No
| |
PWM frequency |
14.11 Hz 56.45 Hz 112.90 Hz 225.80 Hz 451.59 Hz 1806.37 Hz
|
14.11 Hz 56.45 Hz 112.90 Hz 225.80 Hz 451.59 Hz 1806.37 Hz
| |
PWM cyclic ratio |
0 →100 % (256 steps for CD, XD and 1024 for XA)
|
0 →100 % (256 steps for CD, XD and 1024 for XA)
| |
PWM accuracy at 120 Hz |
< 5 % (20 % →80 %) load at 10 mA
|
< 5 % (20 % →80 %) load at 10 mA
| |
Max. Breaking current PWM |
50 mA
|
50 mA
| |
Max. cable length PWM |
20 m
|
20 m
| |
PWM accuracy at 500 Hz |
< 10 % (20 % →80 %) load at 10 mA
|
< 10 % (20 % →80 %) load at 10 mA
| |
Status indicator |
On LCD screen for CD and XD
|
On LCD screen for CD and XD
|
Accessories
|
Type |
Description |
Code |
|---|
|
M3 Soft
|
Multilingual programming software containing specific library functions (CD-ROM)
|
88970111
| |
PA
|
EEPROM memory cartridge
|
88970108
| |
PA
|
3 m serial link cable : PC →Millenium 3
|
88970102
| |
PA
|
USB cable 3 m : PC →Millenium 3
|
88970109
| |
PA
|
Millenium 3 interface →Bluetooth® (class A 10 m)
|
88970104
|
| Dimensions (mm) |
|---|
| CD20 |  | Zoom |
|